Industrial Civil Installations Ltd.

Customer

Home

Real Estate Agent
___________

Report ID:
___________

Inspection Date  ___________

Inspected By ___________

Client's Contract Agreement

Client name:___________ Home Phone:___________
Address:___________
Work Phone: ___________
Address of property to be inspected: ___________

This agreement is made between Industrial Civil Installations Ltd. "(ICI Ltd.)" And the "client" listed above. ICI Ltd. agrees to conduct a home inspection for the purpose of providing the client with a better understanding of the property conditions as observed at the time of the home inspection. After inspection of the property, ICI Ltd. will provide the client with a written report which will advise the client of any systems or components which in our opinion do not function as intended and/or adversely affect the habitability of the property. Unless otherwise noted below, the client will be provided a written evaluation of the following components of the subject property. SITE GRADING, BUILDING EXTERIOR, ROOFING AND FLASHINGS, FOUNDATION, DECKS AND BALCONIES, BASEMENT OR LOWER LEVEL AREAS, ATTIC AND CRAWL SPACES, HEATING & AIR CONDITIONING SYSTEMS, PLUMBING SYSTEMS, ELECTRICAL SYSTEMS, KITCHEN AND BUILT IN APPLIANCES, INTERIOR CONDITION.
OTHER:

It is understood and agreed that this inspection will be of readily accessible areas of the building and is limited to visual observations of apparent condition existing at the time of the inspection only. Latent or concealed defects and deficiencies are excluded from the inspection. Equipment and systems will not be dismantled in any way to facilitate the inspection.

It is understood and agreed that ICI Ltd. is not an insurer and that the inspection and report are not intended or to be construed as a guarantee or warranty of the adequacy, performance or condition of any structural item or system at the property address. The client hereby releases and exempts ICI Ltd. and its agents and employees of and from any liability and responsibility for the cost of repairing and replacing any unreported defect or deficiency and for any consequential damage, property damage or personal injury of any nature.

This report is not a compliance inspection or certification for governmental codes or regulations of any kind. The inspection and report do not address and are not intended to address the possible presence of, or danger from any potentially harmful substances and environmental hazards including but not limited to radon gas, lead paint, asbestos, urea formaldehyde, toxic chemicals, water and airborne hazards, soil evaluation, flood plain location, efficiency or the capacity of each building to meet the needs of the client. Also excluded are inspections of and report on swimming pools, wells, water quality, septic systems, security systems, water softeners, sprinkler systems and the presence of rodents, termites and other insects.

It is recognized that the client cannot always be present at the home inspection, therefore, the client and ICI Ltd. mutually agree to accept facsimile signatures of this contract agreement as original signatures by the parties and, in addition, the parties agree that signatures in counterpart by fax or otherwise will result in a binding agreement between them. A signed copy of this agreement, accompanied by client's payment to ICI Ltd. of the inspection fee shall result in evidence of agreement between the parties, whereupon ICI Ltd. shall proceed with the inspection.

ACCEPTANCE AND UNDERSTANDING OF THIS AGREEMENT ARE HEREBY ACKNOWLEDGED:

Print name:___________________________________ ________________________________________
Signed:______________________________________ Signed:______________________________________

Industrial Civil Installations Ltd.

INVOICE

Customer:
Location:

Inspection Date: 
Report ID:



Real Estate Agent:

Inspection Fee:
ServicePriceAmountSub-Total
Heated Sq Feet 2,001 - 2,500 300.00 1 300.00

Tax $21.00
Total Price $321.00

Payment Options:
X Paid In Full  
  Customer to send payment
  To Be Paid At Closing Attorney: 
Projected Closing Date: 

ROOFING, DRAINAGE, CHIMNEYS

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, Chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components.The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing.The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Styles & Materials
VIEWED ROOF FROM:
WALKED ROOF
ROOF-TYPE:
GABLE
ROOF COVERING:
3-TAB ASPHALT SHINGLES
VENTILATION:
SOFFIT VENTS
TURBINES
CHIMNEY:
METAL FLUE PIPE
BLOCK
SKY LIGHT (S):
NONE



Inspection Items
1.0 ARE THERE ANY NOTICEABLE SWAYS OR SAGS IN THE ROOF SHEATHING
Comments: NO
1.1 ARE THERE MULTIPLE LAYERS OF ROOF COVERINGS
Comments: NO
1.2 DOES THE ROOF COVERING APPEAR TO BE IN SERVICEABLE CONDITION
Comments: Yes, MINOR IMPROVEMENT
Complimentary views. Note photo 5 indicates deterioration of shingles over the rear section of the covered deck only. Seasonal inspection of this area recommended and may require replacement prior to remaining roof.
1.3 IS DRIP EDGE INSTALLED ALONG ROOF PERIMETER
Comments: Yes
1.4 FLASHINGS
Comments: GOOD
1.5 ROOF VENTILATION
Comments: GOOD
1.6 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments: GOOD
1.7 CONDITION OF RAIN GUTTERS
Comments: MINOR IMPROVEMENT
The gutters need cleaning. Recommend installing gutters on missing areas, especially the front, to collect and divert roof drainage away from foundation area.
1.8 ARE DOWNSPOUTS OR DRAINAGE PROVIDED PROPERLY
Comments: MINOR IMPROVEMENT
Missing in areas.
1.9 CHIMNEY
Comments: GOOD
Photo 1. Arrow indicates flue which is permanently blocked with concrete.
Photo 2. A manufactured insulated metal chimney is present which has been dedicated for venting the high efficiency furnace.
1.10 CHIMNEY CROWN
Comments: MINOR IMPROVEMENT
Typical cracks in concrete chimney crown are present. Recommend caulking to minimize potential for water migration into chimney structure.
1.11 CHIMNEY FLUES
Comments: GOOD
Flues are clean.

EAVE, SIDING, FOUNDATION WALLS

The home inspector shall observe: Wall cladding, Flashings, and Trim; Eaves, Soffits, and Fascias; The home inspector shall: Describe wall cladding materials; Probe exterior wood components where deterioration is suspected. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

Styles & Materials
SIDING STYLE:
CHANNEL RUSTIC
STUCCO
SIDING MATERIAL:
CEMENT STUCCO
WOOD



Inspection Items
2.0 CONDITION OF SOFFIT, FASCIA, TRIM AND EAVES
Comments: MINOR IMPROVEMENT
Photo 1. Complimentary view. Photo 2. Gaps in soffit on carport roof will allow birds/insects entry and nesting. Recommend closing with screen.
2.1 CONDITION OF EXTERIOR WALL COVERINGS, FLASHING
Comments: MINOR IMPROVEMENT
Complimentary views (4).
Photo 5. Cracks over rear basement entry door.
2.2 FOUNDATION WALLS AND MORTAR JOINTS (exterior)
Comments: GOOD
2.3 IS OUTSIDE ACCESS TO BASEMENT RODENT PROOF
Comments: Yes

DECKS, BALCONIES, PORCHES, STOOP, STEPS, RAILINGS

The home inspector shall observe: Decks, Balconies, Stoops, Steps, Areaways, Porches and applicable railings.

Styles & Materials
APPURTENANCE:
DECK WITH STEPS
COVERED PORCH
SIDEWALK
PATIO



Inspection Items
3.0 WHAT IS THE CONDITION OF PORCH OR PATIO
Comments: GOOD
Complimentary view.
3.1 DECKS AND HANDRAILS OR BALCONIES
Comments: MINOR IMPROVEMENT
Photo 1. Complimentary view of covered deck area. The paint is failing and repainting of all exposed wood required.
Photo 2. This roof framing is well supported at the 3 exterior sides but support post or collar ties recommended at area indicated by arrow.
3.2 DECK SUPPORTS
Comments: REPAIRS REQUIRED
Corner deck support post is deteriorated at base, full knife blade penetration. Replacement required. Photo 2. Complimentary view of carport support posts.
3.3 DECKS AND HANDRAILS OR BALCONIES (2)
Comments: REPAIRS REQUIRED
Photo 1. Soft areas of floor sheathing present indicating failure of the deck covering material. Repairs are required.
Photo 2. Loose guardrail/handrail present. Deterioration of the wood present, note knife blade penetration at base. The paint is failing and repainting required on all exposed wood surfaces. Repairs are required.
Photo 3. Easy, full depth penetration of knife blade of underlying framing at guardrail post attachment area. Repairs are required.
Photo 4. Deck covering damage and knife blade penetration at base of guardrail post. Repairs required.
3.4 STAIRS AND HANDRAILS
Comments: GOOD
Complimentary view of front stair.
3.5 STAIRS AND HANDRAILS (2)
Comments: REPAIRS REQUIRED
The guardrail/handrail is missing on 1 side and the maximum 4" spacing is exceeded on the existing guardrail. Repairs are required. Deterioration of the wood treads is present in areas. Some areas are visibly rotted and others can be penetrated easily with a knife blade. Immediate repairs are required. Consideration should be given to replacing entire stair structure.

WINDOWS, DOORS

The home inspector shall observe Entryway doors and a representative number of windows. Operate all entryway doors and a representative number of windows. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Presence of safety glazing in doors and windows.

Styles & Materials
ENTRY DOORS:
VARIOUS
STEEL (INSULATED)
WOOD (HOLLOW CORE)
WOOD (SOLID)
INTERIOR DOORS:
HOLLOW CORE
WOOD
WINDOWS:
BOTH
METAL FRAMES
WOOD FRAMES
WINDOW TYPES:
Both
THERMAL/INSULATED
AWNING
DOUBLE SLIDERS
FIXED
WINDOW MANUFACTURER:
UNKNOWN



Inspection Items
4.0 OUTSIDE APPEARANCE OF WINDOWS OR SKYLIGHTS
Comments: MINOR IMPROVEMENT
The paint is failing on the wood framed windows for the dining room. Repainting required.
4.1 SLIDING GLASS DOOR OR PATIO DOORS
Comments: GOOD
Complimentary view.
4.2 CONDITION OF EXTERIOR ENTRY DOORS
Comments: REPAIRS REQUIRED
Minor wear and abrasions present. Repainting required in some areas. Photo 4. The front door sill is significantly deteriorated. Probing indicates deterioration of underlying framing. Immediate repairs are required.
4.3 STORM DOOR AND SCREEN DOOR(S) CONDITION
Comments: GOOD
4.4 IS DOOR CHIME OPERATIONAL
Comments: NO

GARAGE/CARPORT

The home inspector shall observe: Garage door operators; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing. The home inspector is not required to observe: Garage door operator remote control transmitters.

Styles & Materials



Inspection Items
5.0 GARAGE DOOR OPERATORS
Comments: NO
5.1 ANY EXPOSED WIRING ON CEILING LOWER THAN 7 FEET FROM GARAGE FLOOR
Comments: NO
5.2 CONDITION OF CONCRETE SLAB
Comments: MINOR IMPROVEMENT
Typical cracks in concrete slab present. Minor deterioration of concrete surface present in small areas.

DRIVEWAY, RETAINING WALLS, LANDSCAPING

The home inspector shall observe: vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector is not required to observe: Fences; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks.

Styles & Materials
DRIVEWAY:
ASPHALT



Inspection Items
6.0 DOES LANDSCAPE FAVOR PROPER DRAINAGE
Comments: NO
Negative slope towards left side (facing front) and front/left side. These area do not appear to drain water away from home and needs landscaping and drainage corrected. Note gutter missing on front/left section allows roof drainage to fall and collect in this area. Installing gutter to divert roof drainage into existing gutter will substantially minimize amount of water collecting in this area and minimize potential for water infiltration into basement.
6.1 WALKWAY AND DRIVEWAY
Comments: GOOD
Minor settlement and typical cracks in asphalt driveway present.
6.2 CONDITION OF RETAINING WALL(S)
Comments: NOT INSPECTED
6.3 ANY INFREQUENTLY FOUND DISCOVERIES
Comments: NO

ATTIC AND ROOF STRUCTURE

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces.The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances. The home inspector is not required to disturb insulation except when readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs.

Styles & Materials
ATTIC FAN:
NO
HOUSE FAN:
NONE
ATTIC INFO:
SCUTTLE HOLE
INSULATION:
BOTH
BATT
BLOWN
FIBERGLASS
R- VALUE:
R-40 OR BETTER
ROOF STRUCTURE:
ENGINERED WOOD TRUSS
PLYWOOD
SHEATHING
CEILING STRUCTURE:
ENGINEERED TRUSS



Inspection Items
7.0 IS THERE AN ATTIC ACCESS
Comments: Yes, MINOR IMPROVEMENT
Recommend insulating and weatherstripping the attic access.
7.1 IS INSULATION IN ATTIC
Comments: Yes, GOOD
Note mildew on underside of the roof sheathing. It appears this may be from prior to the addition of a turbine roof ventilator when the roof was replaced. The attic ventilation is still minimal and additional ventilation is recommended.
7.2 DO RAFTERS APPEAR TO BE IN GOOD CONDITION
Comments: MINOR IMPROVEMENT
2 adjacent trusses have been cracked. 2 x 4 splices have been installed on 1 side. Recommend additional splice at each location well nailed and extending a minimum of 3' each way past the damage.
7.3 ARE THERE ANY VISIBLE SIGNS OF LEAKS OR ABNORMAL CONDENSATION
Comments: Yes, MINOR IMPROVEMENT
Refer to 7.1 photo and comments.
7.4 IS THERE CROSS-VENTILATION
Comments: Yes, MINOR IMPROVEMENT
Refer to photo and comments 7.1
7.5 ARE THERE ANY VISIBLE SIGNS OF DETERIORATION
Comments: NO
7.6 IS THERE ANY DEBRIS IN ATTIC
Comments: NO
7.7 ARE THERE ANY UNSAFE ELECTRICAL WIRING IN ATTIC
Comments: NO
7.8 B-VENT IN ATTIC
Comments: GOOD
Complimentary view.
7.9 KITCHEN AND BATHROOM VENTING IN ATTIC
Comments: MINOR IMPROVEMENT
The kitchen exhaust duct does not vent to the exterior.

KITCHEN (Coverings, Windows, Outlets and Doors)

The home inspector shall observe: Walls, ceiling, and floors; and a representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments; Move personal items, panels, furniture, equipment, plant life or debris that obstructs accerss or visibility.

Styles & Materials
CEILING MATERIAL:
SUSPENDED CEILING PANELS
WALL MATERIAL:
DRYWALL
WALLPAPER
FLOOR COVERING(S):
VINYL



Inspection Items
8.0 KITCHEN COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
8.1 CEILING
Comments: MINOR IMPROVEMENT
Minor wear and abrasions are present. Moisture stains are present which appear to be due to high moisture in kitchen or surface splashing.
8.2 WALLS
Comments: GOOD
8.3 FLOOR
Comments: MINOR IMPROVEMENT
Minor wear and abrasions are present.
8.4 PANTRY OR CL0SET DOORS
Comments: GOOD
8.5 WINDOWS
Comments: GOOD
8.6 OUTLETS AND WALL SWITCHES CONDITION
Comments: GOOD

KITCHEN COMPONENTS, WASHER/DRYER CONNECTIONS

The home inspector shall observe Counters and a representative number of installed cabinets; and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.

Styles & Materials
CABINETRY:
MELAMINE
WOOD TRIM
COUNTERTOP:
LAMINATE
DISHWASHER:
GENERAL ELECTRIC
DISPOSER:
NONE
RANGE/OVEN:
MOFFAT
EXHAUST/RANGE:
KENMORE
BUILT-IN MICROWAVE:
NONE
REFRIGERATOR:
MAYTAG
WASHER DRAIN SIZE:
1 1/2" DIAMETER (undersized)
DRYER VENT:
FLEXIBLE VINYL
DRYER POWER SOURCE:
22O ELECTRIC



Inspection Items
9.0 KITCHEN FIXTURES AND APPLIANCES (over-all)
Comments: GOOD
9.1 CONDITION OF PLUMBING UNDER SINK
Comments: GOOD
9.2 ARE CUT-OFF VALVES UNDER SINK
Comments: Yes
9.3 FAUCET AND SPRAY NOZZLE CONDITION
Comments: GOOD
9.4 IS DISPOSER OPERATIONAL
Comments: NOT INSPECTED
9.5 COOKTOP/OVEN OR RANGE OPERATIONAL
Comments: GOOD
9.6 RANGE VENTILATION OPERATIONAL
Comments: NO, REPAIRS REQUIRED
The exhaust fan does not work.
9.7 IS THE OUTLET FOR REFRIGERATOR 3 PRONG GROUNDED OR ACCESSIBLE
Comments: Yes
9.8 ARE THE OUTLETS WITHIN TWO FEET OF THE SINK GROUNDED
Comments: Yes
9.9 CABINETS CONDITION
Comments: GOOD
9.10 CONDITION OF COUNTERTOP
Comments: MINOR IMPROVEMENT
The counter end cap is taped on. Repairs are required.
9.11 IS DISHWASHER OPERATIONAL
Comments: Yes
9.12 WASHER/DRYER CONNECTIONS
Comments: GOOD
Complimentary view laundry room.

DINING ROOM (Coverings, Windows, Outlets and Doors)

Styles & Materials
CEILING MATERIAL:
DRYWALL TEXTURED
WALL MATERIAL:
DRYWALL
WOOD
FLOOR COVERING:
CARPET



Inspection Items
10.0 DINING ROOM COMPLIMENTARY VIEW
Comments: Yes
Complimentary view.
10.1 CEILING
Comments: GOOD
10.2 WALLS
Comments: GOOD
10.3 FLOOR
Comments: MINOR IMPROVEMENT
Minor stains present may be removed by cleaning.
10.4 DOORS
Comments: MINOR IMPROVEMENT
The sliding patio door screen is missing.
10.5 WINDOWS
Comments: GOOD
10.6 OUTLETS AND WALL SWITCHES CONDITION
Comments: GOOD

LIVING ROOM

Styles & Materials
CEILING MATERIAL:
DRYWALL TEXTURED
WALL MATERIAL:
DRYWALL
WOOD
FLOOR COVERING:
CARPET



Inspection Items
11.0.A LIVING ROOM COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
11.1.A CEILING
Comments: GOOD
11.2.A WALLS
Comments: GOOD
11.3.A FLOORS
Comments: MINOR IMPROVEMENT
Minor stains present may be removed by cleaning.
11.4.A CLOSET DOORS
Comments: NO
11.5.A WINDOWS
Comments: GOOD
11.6.A OUTLETS AND WALL SWITCHES CONDITION
Comments: GOOD

DOWNSTAIRS FAMILY ROOM

Styles & Materials
CEILING MATERIAL:
PANELING
WALL MATERIAL:
WOOD
FLOOR COVERING:
CARPET



Inspection Items
11.0.B LIVING ROOM COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
11.1.B CEILING
Comments: MINOR IMPROVEMENT
Several water stains are present along the exterior wall and are likely due to leakage from the wood drip ledge at the base of the exterior sheathing. This ledge seems to be flat or sloping slightly towards the interior and the seal may not be adequate. Repairs may be required. A section of the ceiling has been removed.
11.2.B WALLS
Comments: GOOD
11.3.B FLOORS
Comments: MINOR IMPROVEMENT
Some stains are present which may be removed with cleaning.
11.4.B CLOSET DOORS
Comments: NO
11.5.B WINDOWS
Comments: MINOR IMPROVEMENT
The screen is missing.
11.6.B OUTLETS AND WALL SWITCHES CONDITION
Comments: MINOR IMPROVEMENT
Hot/neutral reverse detected in outlet below missing ceiling section.

DOWNSTAIRS DEN

Styles & Materials
CEILING MATERIAL:
PANELING
WALL MATERIAL:
WOOD
FLOOR COVERING:
CARPET



Inspection Items
11.0.C LIVING ROOM COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
11.1.C CEILING
Comments: GOOD
11.2.C WALLS
Comments: GOOD
11.3.C FLOORS
Comments: GOOD
11.4.C CLOSET DOORS
Comments: NO
11.5.C WINDOWS
Comments: MINOR IMPROVEMENT
The screen is missing.
11.6.C OUTLETS AND WALL SWITCHES CONDITION
Comments: MINOR IMPROVEMENT
Hot/neutral reverse detected in outlet below missing ceiling section.

BEDROOMS (Coverings, Windows, Outlets and Doors)

Styles & Materials
CEILING MATERIAL:
DRYWALL TEXTURED
WALL MATERIAL:
DRYWALL
FLOOR COVERING:
CARPET
CLOSET DOORS:
HOLLOW CORE
BIFOLDS



Inspection Items
12.0 BEDROOMS COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
12.1 CEILING
Comments: GOOD
12.2 WALLS
Comments: MINOR IMPROVEMENT
Drywall damaged where door knob has hit wall. Minor wear and abrasions present.
12.3 FLOORS
Comments: GOOD
12.4 DOORS
Comments: MINOR IMPROVEMENT
Minor wear and abrasions are present. The closet door is missing in the front center bedroom.
12.5 WINDOWS
Comments: MINOR IMPROVEMENT
The screens are missing in the front center and rear corner bedrooms.
12.6 OUTLETS AND WALL SWITCHES CONDITION
Comments: GOOD

UPSTAIRS BATH

Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
TILE PANELING
VINYL TUB SURROUND
FLOOR COVERING:
CERAMIC TILE



Inspection Items
13.0.A COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
13.1.A CEILING
Comments: GOOD
13.2.A WALLS
Comments: GOOD
13.3.A FLOORS
Comments: GOOD
13.4.A DOORS
Comments: MINOR IMPROVEMENT
Minor wear and abrasions are present.
13.5.A WINDOWS
Comments: MINOR IMPROVEMENT
The screen is missing.
13.6.A ARE BATHROOM OUTLETS GFCI PROTECTED
Comments: Yes

DOWNSTAIRS BATH

Styles & Materials
CEILING MATERIAL:
WOOD
WALL MATERIAL:
WOOD
FLOOR COVERING:
VINYL TILE



Inspection Items
13.0.B COMPLIMENTARY VIEW
Comments: Yes
Complimentary views.
13.1.B CEILING
Comments: MINOR IMPROVEMENT
Unfinished area above shower.
13.2.B WALLS
Comments: GOOD
13.3.B FLOORS
Comments: GOOD
13.4.B DOORS
Comments: GOOD
13.5.B WINDOWS
Comments: MINOR IMPROVEMENT
1 pane is cracked and the screen is missing.
13.6.B ARE BATHROOM OUTLETS GFCI PROTECTED
Comments: NOT INSPECTED

BATHROOM COMPONENTS

Styles & Materials
EXHAUST FAN TYPES:
FAN ONLY



Inspection Items
14.0 CONDITION OF SINK BASE AND CABINETRY
Comments: MINOR IMPROVEMENT
One of the drawer fronts is broken.
14.1 CONDITION OF PLUMBING FIXTURES
Comments: MINOR IMPROVEMENT
The tub has been painted and the new paint is peeling off.
14.2 ARE CUT-OFF VALVES UNDER SINK AND TOILET
Comments: Yes
14.3 DOES SINK PLUMBING OPERATE PROPERLY
Comments: Yes
14.4 SINK FAUCETS AND STOP VALVE
Comments: GOOD
14.5 DOES TOILET OPERATE PROPERLY
Comments: Yes
14.6 DOES SHOWER/BATH DRAIN PROPERLY
Comments: Yes
14.7 SHOWER AND TUB FAUCETS AND STOP VALVE
Comments: GOOD
14.8 CAULKING ALONG PERIMETER OF TUB/SHOWER AND FLOOR
Comments: GOOD
14.9 EXHAUST FAN
Comments: GOOD

INTERIOR STAIRS, RAILINGS AND BALCONIES

The home inspector shall observe: Steps, stairways, balconies, and railings

 



Inspection Items
15.0 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments: GOOD
Complimentary view.
15.1 ARE STEPS UNIFORM IN HEIGHT
Comments: Yes
15.2 ARE GUARDRAILS SECURE
Comments: Yes
15.3 ARE PICKETS SPACED 4 INCHES APART OR LESS (Safety issue for children)
Comments: NO, MINOR IMPROVEMENT
The picket spacing is greater than the 4" maximum.

ELECTRICAL

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main overcurrent device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their overcurrent devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any overcurrent device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Styles & Materials
ELECTRICAL CONDUCTORS:
ABOVE GROUND
PANEL CAPACITY:
100 AMP
PANEL TYPE:
CIRCUITS
WIRING METHODS:
LOOMEX
BRANCH WIRE 15 and 20 AMP:
COPPER



Inspection Items
16.0 SERVICE ENTRANCE CONDUCTORS
Comments: MINOR IMPROVEMENT
Excessive tension of the electric service line is pulling the anchor loose. Recommend BC Hydro inspect and repair as required.
16.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Comments: GOOD
Complimentary view.
16.2 BOND WIRE FROM ELEC PANEL TO METAL PLUMBING
Comments: Yes
16.3 CONDITION OF WIRING, CIRCUITS, OR FUSES INSIDE MAIN PANEL (Branch circuit conductors, Over-current devices, and compatibility of their amperage and voltage)
Comments: REPAIRS REQUIRED
Problem(s) discovered with branch circuits such as doubled wiring at circuit breakers, and any other problems that an electrician may discover while performing repairs need correcting. Recommend a licensed electrician inspect further and correct as needed.
16.4 ARE THE CIRCUITS OR FUSES LABELED CLEARLY
Comments: NO, MINOR IMPROVEMENT
Some labels are present, but illegible or confusing. Recommend correcting for safety reasons.
16.5 ARE THE CIRCUIT BREAKERS THE SAME BRAND NAME AS PANEL
Comments: Yes
16.6 LOCATION OF MAIN AND DISTRIBUTION PANELS
Comments: MINOR IMPROVEMENT
The main breaker panel is located behind wood cover which is screwed in place. Panel cover should be readily accessible.
16.7 ARE SMOKE DETECTORS PRESENT IN HOME
Comments: Yes, REPAIRS REQUIRED
A smoke detector is installed on the upper floor but none were found in the basement. Smoke detectors are required on all floors immediately adjacent to sleeping areas and should be interconnected on a 120 volt dedicated circuit. The existing smoke detector was not functional.
16.8 CONNECTED DEVICES, FIXTURES OR LOOSE WIRING (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: GOOD
16.9 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments: GOOD
16.10 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments: MINOR IMPROVEMENT
Exterior outlets should be upgraded to GFCI outlets.

STRUCTURAL COMPONENTS

The Home Inspector shall observe and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components; and structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Move insulation where readily visible evidence indicates the need to do so; and Move insulation where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or it's components or be dangerous to or adversely effect the health of the home inspector or other persons.

Styles & Materials
FOUNDATION:
POURED CONCRETE
FLOOR STRUCTURE:
2 X 10
WOOD JOISTS
WALL STRUCTURE:
WOOD FRAMED



Inspection Items
17.0 FOUNDATION WALLS
Comments: GOOD
None of the interior of the foundation was visible. Thorough inspection of all visible areas of the exterior foundation found no concerns.
17.1 FLOOR STRUCTURE
Comments: GOOD
17.2 GIRDERS, PIERS, COLUMNS AND SUPPORTS
Comments: GOOD
17.3 IS BASEMENT FLOOR CONCRETE SLAB
Comments: Yes
17.4 IS BASEMENT OR CRAWLSPACE CEILING INSULATED
Comments: NO
17.5 ANY DEBRIS IN BASEMENT OR CRAWLSPACE
Comments: NO
17.6 ARE THERE FOUNDATION VENTS OR WINDOWS
Comments: Yes
17.7 ANY WET OR UNUSUALLY DAMP AREA
Comments: NO
17.8 SUMP PUMP
Comments: NO
17.9 WERE SOME AREAS OF BASEMENT OR CRAWLSPACE INACCESSIBLE
Comments: NO

PLUMBING

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps.The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance.The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

Styles & Materials
PLUMBING SUPPLY:
COPPER
DISTRIBUTION:
COPPER
PLUMBING WASTE:
ABS
WATER SOURCE:
PUBLIC
WATER FILTERS:
NONE
WATER HEATER POWER SOURCE:
ELECTRIC
CAPACITY:
UNKNOWN
MANUFACTURER:
UNKNOWN



Inspection Items
18.0 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Comments: GOOD
18.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Comments: GOOD
18.2 ANY LEAKS OR CROSS-CONNECTIONS ON SUPPLY OR WASTE LINES
Comments: NO
18.3 FUNCTIONAL FLOW (water pressure and volume)
Comments: GOOD
18.4 WAS THE MAIN WATER VALVE LOCATED
Comments: Yes
18.5 IS PRESSURE REDUCING VALVE INSTALLED
Comments: NO
18.6 WATER HEATER
Comments: GOOD
Wiring needs to be secured (arrow).
18.7 IS WATER HEATER WIRING SECURED PROPERLY
Comments: NO, MINOR IMPROVEMENT
Wiring for water heater is loose. Recommend a licensed electrician correct as necessary.
18.8 IS THE T&P VALVE PIPED WITHIN 6 INCHES OF FLOOR
Comments: Yes
18.9 CONDITION OF VENT PIPE (from furnace/water heater to chimney)
Comments: NO
18.10 WAS CHIMNEY LINER INSPECTED (for gas water heater only)
Comments: NOT INSPECTED
18.11 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)
Comments: GOOD

HEATING

The home inspector shall observe permanently installed heating systems including: Heating equipment; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type.The home inspector shall operate the systems using normal operating controls.The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

Styles & Materials
NUMBER OF HEAT SYSTEMS (excluding wood):
ONE
FUEL SOURCE:
PROPANE
HEAT TYPE:
FORCED AIR
BTU RANGE:
100000
INPUT BTU
HEAT SYSTEM BRAND:
LENNOX
FILTER TYPE:
WASHABLE
FILTER SIZE:
N/A
DUCTWORK:
NON-INSULATED



Inspection Items
19.0 THERMOSTATS CONDITION
Comments: GOOD
19.1 IS THERE A HUMIDIFIER
Comments: NO
19.2 HEATING EQUIPMENT
Comments: GOOD
Complimentary view.
19.3 COMBUSTION AIR SUPPLY
Comments: GOOD
High efficiency gas furnace has its own closed combustion air supply. Combustion air supply is needed for the wood burning fireplaces. Recommend installation of a 5" (minimum) insulated duct from the exterior to terminate adjacent to the furnace.
19.4 NORMAL OPERATING CONTROLS
Comments: GOOD
19.5 AUTOMATIC SAFETY CONTROLS
Comments: GOOD
19.6 CHIMNEYS, FLUES AND VENTS (FOR FURNACE)
Comments: GOOD
19.7 HEAT DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: GOOD
19.8 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Comments: GOOD

FIREPLACES

Styles & Materials
TYPES OF FIREPLACES:
CONVENTIONAL
OPERABLE FIREPLACES:
TWO
NUMBER OF WOODSTOVES:
NONE



Inspection Items
20.0 FIREPLACE OR SOLID FUEL BURNING DEVICES
Comments: GOOD
Both fireplaces have had very little use.
20.1 CLEARANCE TO COMBUSTIBLES
Comments: GOOD
20.2 IS THERE A DAMPER
Comments: Yes
20.3 CONDITION OF HEARTH, MANTLE AND WALL
Comments: GOOD
20.4 DO THE FIRE-BRICK WALLS NEED MORTAR OR REPAIR
Comments: NO
20.5 WAS LINER INSPECTED OR FULLY VISIBLE FROM END TO END
Comments: Yes
20.6 COMBUSTION AIR SUPPLY
Comments: NO
Combustion air supply is needed if these wood burning fireplaces are to be used.

SUMMARY


Industrial Civil Installations Ltd.

Customer
___________

Home
___________

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitabilty of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation.

This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.

This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

ROOFING, DRAINAGE, CHIMNEYS
1.2 DOES THE ROOF COVERING APPEAR TO BE IN SERVICEABLE CONDITION
Yes, MINOR IMPROVEMENT
Complimentary views. Note photo 5 indicates deterioration of shingles over the rear section of the covered deck only. Seasonal inspection of this area recommended and may require replacement prior to remaining roof.
1.7 CONDITION OF RAIN GUTTERS
MINOR IMPROVEMENT
The gutters need cleaning. Recommend installing gutters on missing areas, especially the front, to collect and divert roof drainage away from foundation area.
1.8 ARE DOWNSPOUTS OR DRAINAGE PROVIDED PROPERLY
MINOR IMPROVEMENT
Missing in areas.
1.10 CHIMNEY CROWN
MINOR IMPROVEMENT
Typical cracks in concrete chimney crown are present. Recommend caulking to minimize potential for water migration into chimney structure.

EAVE, SIDING, FOUNDATION WALLS
2.0 CONDITION OF SOFFIT, FASCIA, TRIM AND EAVES
MINOR IMPROVEMENT
Photo 1. Complimentary view. Photo 2. Gaps in soffit on carport roof will allow birds/insects entry and nesting. Recommend closing with screen.
2.1 CONDITION OF EXTERIOR WALL COVERINGS, FLASHING
MINOR IMPROVEMENT
Complimentary views (4).
Photo 5. Cracks over rear basement entry door.

DECKS, BALCONIES, PORCHES, STOOP, STEPS, RAILINGS
3.1 DECKS AND HANDRAILS OR BALCONIES
MINOR IMPROVEMENT
Photo 1. Complimentary view of covered deck area. The paint is failing and repainting of all exposed wood required.
Photo 2. This roof framing is well supported at the 3 exterior sides but support post or collar ties recommended at area indicated by arrow.
3.2 DECK SUPPORTS
REPAIRS REQUIRED
Corner deck support post is deteriorated at base, full knife blade penetration. Replacement required. Photo 2. Complimentary view of carport support posts.
3.3 DECKS AND HANDRAILS OR BALCONIES (2)
REPAIRS REQUIRED
Photo 1. Soft areas of floor sheathing present indicating failure of the deck covering material. Repairs are required.
Photo 2. Loose guardrail/handrail present. Deterioration of the wood present, note knife blade penetration at base. The paint is failing and repainting required on all exposed wood surfaces. Repairs are required.
Photo 3. Easy, full depth penetration of knife blade of underlying framing at guardrail post attachment area. Repairs are required.
Photo 4. Deck covering damage and knife blade penetration at base of guardrail post. Repairs required.
3.5 STAIRS AND HANDRAILS (2)
REPAIRS REQUIRED
The guardrail/handrail is missing on 1 side and the maximum 4" spacing is exceeded on the existing guardrail. Repairs are required. Deterioration of the wood treads is present in areas. Some areas are visibly rotted and others can be penetrated easily with a knife blade. Immediate repairs are required. Consideration should be given to replacing entire stair structure.

WINDOWS, DOORS
4.0 OUTSIDE APPEARANCE OF WINDOWS OR SKYLIGHTS
MINOR IMPROVEMENT
The paint is failing on the wood framed windows for the dining room. Repainting required.
4.2 CONDITION OF EXTERIOR ENTRY DOORS
REPAIRS REQUIRED
Minor wear and abrasions present. Repainting required in some areas. Photo 4. The front door sill is significantly deteriorated. Probing indicates deterioration of underlying framing. Immediate repairs are required.

GARAGE/CARPORT
5.2 CONDITION OF CONCRETE SLAB
MINOR IMPROVEMENT
Typical cracks in concrete slab present. Minor deterioration of concrete surface present in small areas.

ATTIC AND ROOF STRUCTURE
7.0 IS THERE AN ATTIC ACCESS
Yes, MINOR IMPROVEMENT
Recommend insulating and weatherstripping the attic access.
7.2 DO RAFTERS APPEAR TO BE IN GOOD CONDITION
MINOR IMPROVEMENT
2 adjacent trusses have been cracked. 2 x 4 splices have been installed on 1 side. Recommend additional splice at each location well nailed and extending a minimum of 3' each way past the damage.
7.3 ARE THERE ANY VISIBLE SIGNS OF LEAKS OR ABNORMAL CONDENSATION
Yes, MINOR IMPROVEMENT
Refer to 7.1 photo and comments.
7.4 IS THERE CROSS-VENTILATION
Yes, MINOR IMPROVEMENT
Refer to photo and comments 7.1
7.9 KITCHEN AND BATHROOM VENTING IN ATTIC
MINOR IMPROVEMENT
The kitchen exhaust duct does not vent to the exterior.

KITCHEN (Coverings, Windows, Outlets and Doors)
8.1 CEILING
MINOR IMPROVEMENT
Minor wear and abrasions are present. Moisture stains are present which appear to be due to high moisture in kitchen or surface splashing.
8.3 FLOOR
MINOR IMPROVEMENT
Minor wear and abrasions are present.

KITCHEN COMPONENTS, WASHER/DRYER CONNECTIONS
9.6 RANGE VENTILATION OPERATIONAL
NO, REPAIRS REQUIRED
The exhaust fan does not work.
9.10 CONDITION OF COUNTERTOP
MINOR IMPROVEMENT
The counter end cap is taped on. Repairs are required.

DINING ROOM (Coverings, Windows, Outlets and Doors)
10.3 FLOOR
MINOR IMPROVEMENT
Minor stains present may be removed by cleaning.
10.4 DOORS
MINOR IMPROVEMENT
The sliding patio door screen is missing.

LIVING ROOM
11.3.A FLOORS
MINOR IMPROVEMENT
Minor stains present may be removed by cleaning.

DOWNSTAIRS FAMILY ROOM
11.1.B CEILING
MINOR IMPROVEMENT
Several water stains are present along the exterior wall and are likely due to leakage from the wood drip ledge at the base of the exterior sheathing. This ledge seems to be flat or sloping slightly towards the interior and the seal may not be adequate. Repairs may be required. A section of the ceiling has been removed.
11.3.B FLOORS
MINOR IMPROVEMENT
Some stains are present which may be removed with cleaning.
11.5.B WINDOWS
MINOR IMPROVEMENT
The screen is missing.
11.6.B OUTLETS AND WALL SWITCHES CONDITION
MINOR IMPROVEMENT
Hot/neutral reverse detected in outlet below missing ceiling section.

DOWNSTAIRS DEN
11.5.C WINDOWS
MINOR IMPROVEMENT
The screen is missing.
11.6.C OUTLETS AND WALL SWITCHES CONDITION
MINOR IMPROVEMENT
Hot/neutral reverse detected in outlet below missing ceiling section.

BEDROOMS (Coverings, Windows, Outlets and Doors)
12.2 WALLS
MINOR IMPROVEMENT
Drywall damaged where door knob has hit wall. Minor wear and abrasions present.
12.4 DOORS
MINOR IMPROVEMENT
Minor wear and abrasions are present. The closet door is missing in the front center bedroom.
12.5 WINDOWS
MINOR IMPROVEMENT
The screens are missing in the front center and rear corner bedrooms.

UPSTAIRS BATH
13.4.A DOORS
MINOR IMPROVEMENT
Minor wear and abrasions are present.
13.5.A WINDOWS
MINOR IMPROVEMENT
The screen is missing.

DOWNSTAIRS BATH
13.1.B CEILING
MINOR IMPROVEMENT
Unfinished area above shower.
13.5.B WINDOWS
MINOR IMPROVEMENT
1 pane is cracked and the screen is missing.

BATHROOM COMPONENTS
14.0 CONDITION OF SINK BASE AND CABINETRY
MINOR IMPROVEMENT
One of the drawer fronts is broken.
14.1 CONDITION OF PLUMBING FIXTURES
MINOR IMPROVEMENT
The tub has been painted and the new paint is peeling off.

INTERIOR STAIRS, RAILINGS AND BALCONIES
15.3 ARE PICKETS SPACED 4 INCHES APART OR LESS (Safety issue for children)
NO, MINOR IMPROVEMENT
The picket spacing is greater than the 4" maximum.

ELECTRICAL
16.0 SERVICE ENTRANCE CONDUCTORS
MINOR IMPROVEMENT
Excessive tension of the electric service line is pulling the anchor loose. Recommend BC Hydro inspect and repair as required.
16.3 CONDITION OF WIRING, CIRCUITS, OR FUSES INSIDE MAIN PANEL (Branch circuit conductors, Over-current devices, and compatibility of their amperage and voltage)
REPAIRS REQUIRED
Problem(s) discovered with branch circuits such as doubled wiring at circuit breakers, and any other problems that an electrician may discover while performing repairs need correcting. Recommend a licensed electrician inspect further and correct as needed.
16.4 ARE THE CIRCUITS OR FUSES LABELED CLEARLY
NO, MINOR IMPROVEMENT
Some labels are present, but illegible or confusing. Recommend correcting for safety reasons.
16.6 LOCATION OF MAIN AND DISTRIBUTION PANELS
MINOR IMPROVEMENT
The main breaker panel is located behind wood cover which is screwed in place. Panel cover should be readily accessible.
16.7 ARE SMOKE DETECTORS PRESENT IN HOME
Yes, REPAIRS REQUIRED
A smoke detector is installed on the upper floor but none were found in the basement. Smoke detectors are required on all floors immediately adjacent to sleeping areas and should be interconnected on a 120 volt dedicated circuit. The existing smoke detector was not functional.
16.10 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
MINOR IMPROVEMENT
Exterior outlets should be upgraded to GFCI outlets.

PLUMBING
18.7 IS WATER HEATER WIRING SECURED PROPERLY
NO, MINOR IMPROVEMENT
Wiring for water heater is loose. Recommend a licensed electrician correct as necessary.

Industrial Civil Installations Ltd.

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

Industrial Civil Installations Ltd.